Technical

Type of Low Voltage Distribution System:
TT
TN-C
TN-S
Suitable For:
To protect the systems against the transient overvoltage (lightning)
Nominal AC Voltage of the System (Uo):
230 / 400 V
Maximum Continuous Operating Voltage (Uc):
(L-PE) 275 V
Temporary Overvoltage Test Value (UT):
337 V
Rated Service Short-Circuit Breaking Capacity (Ics):
100 kA
Discharge Current:
Nominal (8 / 20 µs) 20 kA
I (max, 8 / 20 µs) 40 kA
Impulse Current:
I (imp, 10 / 350 µs) 2 kA
Short Circuit Withstand Icc:
100 kA
Arrester Class:
II
Number of Protected Poles:
1
Number of Poles:
1P
Number of Conductors:
1
Transmission Standard:
Optic
Version:
Plug-in
Product Type:
QS
Options Provided:
Residential, commercial building.
Preventive Maintenance Feature:
Yes
Status Indicator:
Yes
Fuse Size:
1 modular spacing
Cross-Section (Across):
Maximum Conductor Solid-Stranded 35 mm²
Maximum Conductor Flexible 25 mm²

Electrical

Rated Voltage (Ur):
230 V AC
Voltage Protection Level ( Up):
1.4 kV
(L-N) 1.4 kV
(N-PE) 1.4 kV
Power Loss:
Total 28 mW

Material Compliance

RoHS Information:
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
RoHS Date:
20230707
REACH Information:
False - does not contain substances > 0.1 mass percentage
REACH Date:
20231212
Conflict Minerals Reporting Template (CMRT):
WEEE Category:
5. Small Equipment (No External Dimension More Than 50 cm)
WEEE B2C / B2B:
Business To Consumer

Environmental

Degree of Protection:
IP20
Maximum Operating Altitude Permissible:
Without Derating 5000

Dimensions

Width in Number of Modular Spacings:
1
Product Net Width:
17.8 mm
Product Net Height:
88 mm
Product Net Depth / Length:
76.7 mm
Product Net Weight:
0.15 kg

Ordering

Package Level 1 Units:
box 1 piece
Package Level 1 Gross Weight:
165 g

Certificates and Declarations

CQC Certificate:
Declaration:

Installation

Mounting Type:
DIN-Rail

Popular Downloads

External Classifications and Standards

ETIM 9:
EC000941 - Surge protection device for power supply systems
ETIM 10:
EC000941 - Surge protection device for power supply systems
UNSPSC:
39121610
eClass:
V11.0 : 27130805
Object Classification Code:
141DCC
Standards:
IEC 61643-11 / EN 61643-11
Vendor INDUSWELL
Type Industrial & Scientific
Sku 2CTB815704R1200
Weight 0.12 kg